National Association of Power Engineers https://www.powerengineers.com Advance your Power Engineering Career. Tue, 24 Aug 2021 18:32:29 +0000 en-US hourly 1 https://wordpress.org/?v=6.7 https://www.powerengineers.com/wp-content/uploads/2020/08/NAPE_Logo_TRANSP-150x150.png National Association of Power Engineers https://www.powerengineers.com 32 32 How to Tackle Boiler Scale with Water Treatment https://www.powerengineers.com/1902/?utm_source=rss&utm_medium=rss&utm_campaign=how-to-tackle-boiler-scale-with-water-treatment Tue, 24 Aug 2021 18:32:22 +0000 https://www.powerengineers.com/?p=1902 Water treatment programs offer wide flexibility in that boiler water treatment can be achieved through precipitating, sequestering or chelating programs.

The post How to Tackle Boiler Scale with Water Treatment first appeared on National Association of Power Engineers.

]]>

The most common water problem developed in steam boiler operations is scale. This involves deposits formed by the precipitation of dissolved solids. The precipitate, along with other suspended solids, is laid down on the metal and heat transfer surfaces as deposit or scale.

Types of Boiler Scale—

Normally, a boiler scale will consist of a combination of several chemical compounds or impurities with one ingredient making up the bulk of the deposit. Hence, it would be extremely rare to encounter a “pure” calcium carbonate, or “pure” calcium sulfate deposit. More often, the deposit will consist of various calcium and magnesium deposits plus lesser amounts of organic matter, iron oxide, silica, etc.
Some more common types of boiler scale:

  • Calcium Carbonate CaCO-3
  • Calcium Sulfate CaSO-4
  • Calcium Silicate CaSiO-3
  • Magnesium Phosphate Mg-3 (PO-4)2
  • Iron Oxide Fe2O3, Fe304, FeO

Boiler deposits can indicate the presence of calcium phosphate, magnesium hydroxide or magnesium silicate, depending on the type of water treatment used and the amount of anions and cations present.

Water Treatment Programs

Treatment programs offer wide flexibility in that boiler water treatment can be achieved through precipitating, sequestering or chelating programs.

  1. Precipitating Program– basically allows for precipitation of calcium as a carbonate or phosphate and the magnesium hardness as a hydroxide or silicate. Sludge conditioning is required to prevent the precipitations from adhering to the heat transfer surfaces.
  2. Sequestering Program– creates a chemical reaction within the boiler water to sequester calcium hardness and disperse iron. Sludge conditioning is required to provide dispersions should upset occur.
  3. Chelating Program– utilizing chelating agents for preventing the usual chemical reactions of calcium and magnesium hardness in scale formation. Chelating agents have been particularly effective in removal of existing scale deposits. Separate iron conditioning is required using organic sludge conditioning.

In total, a balanced or total boiler water treatment program will achieve these objectives:

  • Sufficient alkalinity must be maintained for proper chemical action and to eliminate acidic corrosion.
  • Through the use of sludge conditioners, suspended solids formed, or present will be non-adhering.
  • Suitable oxygen scavengers will remove dissolved oxygen and minimize putting and/or film forming ingredients will be present to provide a protective film on metal surfaces to inhibit corrosion or pitting.


This article was originally featured in the December 1990 issue of The National Engineer, presented by Pennsylvania Chapter 18.

If you have your own expertise you’d like to share with our readers, please email jeannette@powerengineers.com to be featured on our blog.

The post How to Tackle Boiler Scale with Water Treatment first appeared on National Association of Power Engineers.

]]>
The Acidizing Process: 6 Situations to Prepare For https://www.powerengineers.com/1854/?utm_source=rss&utm_medium=rss&utm_campaign=the-acidizing-process-6-situations-to-prepare-for Mon, 02 Aug 2021 14:48:41 +0000 https://www.powerengineers.com/?p=1854 What to be aware of with steam boiler water-side acidizing.

The post The Acidizing Process: 6 Situations to Prepare For first appeared on National Association of Power Engineers.

]]>

Originally published in V95, Number 1 of the National Engineer
Presentation by Dave Ohman to NAPE-Union Grove Wisconsin, 1991.


What is Acidizing
Boiling water eventually produces a scale deposit in the teapot. If this deposit is objectionable, you may either buy a new teapot or “acidize” it by boiling table vinegar in the pot. This cleaning activity is usually successful, but the smell remaining in the house may be unpleasant. The small cost of buying a new teapot may persuade you not to acidize it.
 
This same type of water scale deposit occurs in steam boilers. However, in the case of the boiler, it is a lot less expensive to acidize than buy a new one.
 
Perhaps obtaining a few drums of acid, dumping the acid into the boiler, and allowing the acid to soak for a few hours or overnight may sound like a cheap resolve. You may be able to find a contractor that will do this for you. But it may not work out as well as you expect.
 
Beware of these situations:
 
–          Having drums of acid stored and handled in your building can be a nuisance and a potential pollution liability that could be avoided by use of a bulk tank truck outside.

–          When you receive the drums in your building, you may unknowingly become the owner of the acid and therefore completely responsible for any mishaps, damage, or pollution. A suggestion would be to have the contractor keep the drums or bulk acid on his truck outside and have a signed contract that states that the contractor will be responsible for the acid or any waste stream at all times.

–          Remember stinking up the house when cleaning the teapot? Perhaps vacuum containment and a method of scrubbing these fumes would be of benefit.

–          If a leak is encountered during the acidizing, where will this large volume of acid and water mixture go? There should be an empty container on site that is large enough to contain the entire solution volume. Transferring the leaking solution to this container would give enough time to make repairs, and/or properly neutralize the solution.

–          If and when the acid leaks out and there is no container available, at least two problems occur. First there is a pollution problem and then you find that the boiler is not clean yet. The contractor will advise that he must go obtain more chemical and try another day at additional cost! This type of work should be done on a firm price basis with guaranteed clean results.

–          The contractor may tell you that there is no need to haul this solution away for legal disposal. He may advise that neutralizing on site is all that needs to be done. The Federal Law states that the cleaning site must possess a hazardous treatment facility that is licensed and permitted to do such neutralization.  

Learn more about Boiler Plant Operation by signing up for our online courses, or request a demo today.

The post The Acidizing Process: 6 Situations to Prepare For first appeared on National Association of Power Engineers.

]]>
A View Point: Two Keys to Improve Plant Safety https://www.powerengineers.com/1816/?utm_source=rss&utm_medium=rss&utm_campaign=a-view-point-two-keys-to-plant-safety Mon, 19 Jul 2021 17:02:15 +0000 https://www.powerengineers.com/?p=1816 Originally published in V102, Number 4 of the National EngineerBy Mark Crisco | Member of Piedmont, NC Chapter#1, June 1998 If neglected in condition or operation, a large industrial water tube boiler is potentially the single most dangerous piece of equipment a company could possess. However, properly maintained and operated, these boilers are in some… Read More »A View Point: Two Keys to Improve Plant Safety

The post A View Point: Two Keys to Improve Plant Safety first appeared on National Association of Power Engineers.

]]>
Originally published in V102, Number 4 of the National Engineer
By Mark Crisco | Member of Piedmont, NC Chapter#1, June 1998


If neglected in condition or operation, a large industrial water tube boiler is potentially the single most dangerous piece of equipment a company could possess. However, properly maintained and operated, these boilers are in some ways, no more or less dangerous than many other types of industrial equipment. The key word here is “properly”. If boiler conditions, both operational and material, are not properly maintained, the then potential for a catastrophic accident greatly increases, endangering all who are unfortunate enough to be near the plant.

Those of us who have seen furnace explosions, flare backs, oil and electrical fires, and large high-pressure steam leaks, are well-educated and respectful of safe operational procedures. Sometimes in the past, we may have become somewhat “stale” in our duties to routine; and between long running times when no major problems appear on the horizon.

Because of this, we should show resolve and be vigilant in our responsibility to preform our jobs at a higher safer level; to benefit our co-workers, our plants and our companies. There are a thousand or more hazardous situations that could develop in a steam or power plant. Plant personnel are expected to respond swiftly, correctly, and safely to all these various abnormal conditions.

Clear communications among plant personnel are essential to determine what is or isn’t a safe action or safe condition. Communication is a major key in maintaining plant safety at all times.

Teamwork is another major ley in this area and is necessary to bring everything together.

No organization has reached the point yet where improvements can’t be made upon either of these two elements.

Improving can be an on-going process, not only in improving plant equipment conditions, but also to personnel improving professionally. To help prevent casualty and/or accident scenarios from occurring, and to maintain a high state of plant operational readiness, our keys need to be utilized. They are Communication and Teamwork.

What is the result of turning these keys? Smooth, efficient, and safe plant operations. And safety here is first, never last. For you cannot put a price tag on safety. Safety takes a back seat to nothing or no one. If it is not this way, then from my viewpoint—we are al l just one roll of a dice away from disaster!

Want to learn more?
N.A.P.E.’s Safety Course covers various of important OSHA regulations. Make sure that your team understands the importance of work-place safety so that your facility runs smoothly and efficiently.

The post A View Point: Two Keys to Improve Plant Safety first appeared on National Association of Power Engineers.

]]>
How to Service Dirty Coils https://www.powerengineers.com/1791/?utm_source=rss&utm_medium=rss&utm_campaign=how-to-service-dirty-coils Thu, 15 Jul 2021 17:37:37 +0000 https://www.powerengineers.com/?p=1791 How to properly clean dirty condenser coils and the risks of using foaming cleansers.

The post How to Service Dirty Coils first appeared on National Association of Power Engineers.

]]>
(Originally an excerpt from NY24’s “Phoenix”. Published in V102, Number 5 of the National Engineer)


This may sound like a subject that’s too simple to discuss, yet there’s much to learn. Here are three common service problems:

  1. Most service technicians carry no tools to actually read pressure drops.
  2. Many common coil-cleaning methods are poor and some damage both coils and people.
  3. Hardly anyone, including manufacturers, know what to do about stinking evaporator coils.

WHEN A COIL IS CLOGGED. This sounds like an easy problem. All you have to do is look… right? I’ve been on many jobs where a recently cleaned coil looked spotless on the surface. Yet, upon further examination, the inner rows were completely clogged with grease or small particulate matter.

On one such job, the symptom was an unusually high number of condenser coil. The problem as complicated by the fact that the most recent motor to fail was totally-open instead of the recommended top-enclosed type. This led me to believe the failure was caused by rain entering the motor windings (which did happen, but it wasn’t the cause of the repeat failures).

After replacing the motors with the correct type, it also failed within 48 hours.

Although nothing was noticeable on the coil surface, the pressure on the inside of the condenser (in relation to the atmospheric pressure) revealed a static pressure of .5in. wg. magnehelic.

For most residential and light commercial machines using propeller-type fans, this is considerable higher than what the pressure across the coil surface should be. Maximum static pressure probably shouldn’t exceed .2-in. Due to the horsepower leading to early failure.

With centrifugal evaporator fans, however, a clogged coil won’t cause motor failure. The reason for this is, again, the centrifugal fan’s horsepower curve.

The symptoms of restricted airflow through an evaporator coil is low suction pressure and frost on the coil. This is one example where low air flow may not provide a large temperature drop between entering and leaving air. Why not? Such clogging disables whole sections of the coil, affecting thermal transfer.

Again, use a magnehelic or other air pressure measuring device to determine pressure-drop across the evaporator coil. The manufacturer’s design for a clean coil should be determined from their specifications. This varies according to design, fan speed, and whether the coil is wet or dry. Experience with residential and light commercial jobs show that most clean evaporators never exceed a static-pressure drop of .5-in. A good average would be >3-in. with a clean, dry coil.

COIL CLEANING. So what should you use to clean the coil? Perhaps I should start out by telling you what not to use. One of the most popular chemicals for cleaning condenser coils is something called a brightener. This cleaner typically foams when it hits the coil surface. It is popular because (supposedly):

  • The foaming removes deep dirt.
  • It removes the outer crust providing the coil better heat transfer.
  • It brightens the coils surface, making it look like new.

That’s the bright side. However, the foaming is caused by a chemical reaction between the acid and the aluminum fins.

If you hold a burning match to the foam (please don’t try it), you’ll discover a highly-explosive hydrogen content of the bubbles. The coil surface is brightened because the protective outer oxide coating is removed—but just temporarily.

I discourage this use of corrosive foaming coil cleaners because:

  • They are extremely hazardous—accidental misuse can cause burns and blindness.
  • They destroy the aluminum fins—each acid cleaning removes an average ½ oz of fin material from a typical coil.

They rapidly degrade the bond between the aluminum fins and the copper tubes by accelerating electrolysis, permanently lower coil efficiency and life.

What about foaming cleaners with labels saying “non-acid?” In most cases, the active ingredient here is a very strong, very active alkali. The hazards and results are the same as acid cleaners.

So, what should you use? Well, most safe cleaners won’t provide results as the corrosives. They won’t foam upon hitting the coil surface, nor will they brighten the aluminum—but they will do a good job if allowed to soak in. There are many fine detergents on the market, as well as some good cleaning methods. The trick is to use the right method and cleaner for each situation.

If the problem is just a surface loaded with debris, a vacuum cleaner with a small brush and crevice tool is your best bet.

Where grease is the problem, soaking the coil with a degreaser and letting it sit for a while before rinsing is a sensible solution. High pressure cleaning with a good cleanser, blowing outward from the inside, is the most effective way to clean deeply loaded coils.

Many service mechanics are reluctant to clean spine-type coils with high-pressure hoses because they’re afraid of bending the spines. Actually, other than for aesthetic reasons, this should be of little concern. Tests by one of the manufacturers showed that in a worse case situation affecting all front and rear surfaces, bending spine fins will degrade total efficiency less than 10%. Of course, this isn’t true of plate fin coils.

Article originally published from the July 1998 issue of the National Engineer.
Photo Credit: “A/C Tune up check” by jackiebese is licensed under CC BY-SA 2.0

Interested in learning More?

Check out our Refrigeration and AC Plant Operation Online Course.

The post How to Service Dirty Coils first appeared on National Association of Power Engineers.

]]>